Skip to content

Unit error in QCrit #139

Description

@FWuellhorst

Describe the bug
QCrit in DHW is without unit but meant to be in kWh, but in Joule in the distribution module.
Thus, QCrit = 2.24 is essentially divided by 3600000 leading to the additional design size due to DHW according to 15450 which are close to zero.

This was introduced in a late commit of the latest main update, so only results created since the last main update are affected.